Calculate voltage drop across a wire run. Shows voltage drop in volts and percentage. Checks compliance with KEC indoor (3%) and outdoor (5%) limits.
Input
Result
End Voltage
Indoor standard (≤3%)
Outdoor standard (≤5%)
Enter all fields to calculate.
Formula: ΔV = (2×I×L×ρ)/A (single), (√3×I×L×ρ)/A (three-phase). Cu ρ=0.0175, Al ρ=0.028 Ω·mm²/m